Simplex XL Mixing Valve - Specification For TWDTSXL

The Digital Tempering System components shall conform to ASSE 1017, CA lead-free plumbing law, and CSA B 125.3. System shall include piping for hot, cold, tempered, recirc, and boiler feed. Components shall include 120V digital controller, 304SS piston design mixing valve, 304SS temperature sensor, external 24V worm-gear type actuator, thermal safety valve, check valves, and ball valves. System shall be a Towle Whitney model TWDTSXL (800-807-9827). Option: System shall include a (Internet, BACnet, ModBus) module for remote communication.

Home Simplex XL Mixing Valve

Duplex Mixing Valve - Specification For TWDTSD

The Digital Tempering System components shall conform to ASSE 1017, CA lead-free plumbing law, and CSA B 125.3. System shall include piping for hot, cold, and tempered line. Components shall include 120V digital controller, (2) 304SS piston design mixing valves, 304SS temperature sensor, (2) external 24V worm-gear type actuator, thermal safety valve, check valves, ball valves, and disconnect couplings (SharkBite/Grooved). System shall be a Towle Whitney model TWDTSD (800-807-9827). Option: System shall include a (Internet, BACnet, ModBus) module for remote communication.